1065 Alternate True Power Factor, Phase B 0.001 0 to 2,000
1066 Alternate True Power Factor, Phase C 0.001 0 to 2,000
1067 Alternate True Power Factor, Total 0.001 0 to 2,000
1-Second Real-Time Readings
1100 Current, Phase A A Amps/Scale 0 to 32,767
1101 Current, Phase B A Amps/Scale 0 to 32,767
1102 Current, Phase C A Amps/Scale 0 to 32,767
1103 Current, Neutral B Amps/Scale 0 to 32,767
1104 Current, Ground C Amps/Scale 0 to 32,767
1105 Current, 3-Phase Average A Amps/Scale 0 to 32,767
1106 Current, Apparent RMS A Amps/Scale 0 to 32,767
1107 Current, Unbalance, Phase A 0.10% -1,000 to 1,000
1108 Current, Unbalance, Phase B 0.10% -1,000 to 1,000
1109 Current, Unbalance, Phase C 0.10% -1,000 to 1,000
1110 Current, Unbalance, Max 0.10% -1,000 to 1,000
1120 Voltage, A-B D Volts/Scale 0 to 32,767
1121 Voltage, B-C D Volts/Scale 0 to 32,767
1122 Voltage, C-A D Volts/Scale 0 to 32,767
1123 Voltage, L-L Average D Volts/Scale 0 to 32,767
1124 Voltage, A-N D Volts/Scale 0 to 32,767
1125 Voltage, B-N D Volts/Scale 0 to 32,767
1126 Voltage, C-N D Volts/Scale 0 to 32,767
1127 Voltage, N-G E Volts/Scale 0 to 32,767
1128 Voltage, L-N Average D Volts/Scale 0 to 32,767
1129 Voltage, Unbalance, A-B 0.10% -1,000 to 1,000
1130 Voltage, Unbalance, B-C 0.10% -1,000 to 1,000
1131 Voltage, Unbalance, C-A 0.10% -1,000 to 1,000
1132 Voltage, Unbalance, Max L-L 0.10% -1,000 to 1,000
1133 Voltage, Unbalance, A-N 0.10% -1,000 to 1,000
1134 Voltage, Unbalance, B-N 0.10% -1,000 to 1,000
1135 Voltage, Unbalance, C-N 0.10% -1,000 to 1,000
1136 Voltage, Unbalance, Max L-N 0.10% -1,000 to 1,000
1140 Real Power, Phase A F kW/Scale -32,767 to 32,767
1141 Real Power, Phase B F kW/Scale -32,767 to 32,767
1142 Real Power, Phase C F kW/Scale -32,767 to 32,767
1143 Real Power, Total F kW/Scale -32,767 to 32,767
Table A3:Abbreviated Register List
Register
Number
Description
Scale
Factor
Units Register Range
See How Power Factor is Stored in the Registeron page 128.
The alternate storage method for power factor (PF) is useful for outputting PF on analog outputs. The PF value is stored as a positive value
between 0 and 2, centered around 1 (unity). A value of 0 lagging maps to 0; -0.999 maps to 0.999;0.999 leading maps to 1.001; and 0 leading
maps to 2. The alternate PF is also stored with a scale factor 0.001.
These configuration registers require that you enter the setup mode to change the registers contents. Issue command 9020 to enter setup
mode and 9021 to exit setup mode. See Using the Command Interface to Change Configuration Registers on page 187 for instructions on
how to use the setup-mode commands.
Quantity available for 4-wire system only. Value set to -32,768 if not available.