63230-300-212 Chapter 6—Alarms
April 2001 Alarm Conditions and Alarm Numbers
95
© 2001 Schneider Electric All Rights Reserved
43 Over THD Voltage B–C Over THD Vbc 1212 Tenths % — 010
44 Over THD Voltage C–A Over THD Vca 1213 Tenths % — 010
45-80 Reserved for custom alarms. —————
High Speed Alarms (100 ms)
01 Over Current A Over Ia HS 1,000 Amperes A 010
02 Over Current B Over Ib HS 1001 Amperes A 010
03 Over Current C Over Ic HS 1002 Amperes A 010
04 Over Current N Over In HS 1003 Amperes B 010
05 Over Current G Over Ig HS 1004 Amperes C 010
06 Over Voltage A–N Over Van HS 1024 Volts D 010
07 Over Voltage B–N Over Vbn HS 1025 Volts D 010
08 Over Voltage C–N Over Vcn HS 1026 Volts D 010
09 Over Voltage A-B Over Vab HS 1020 Volts D 010
10 Over Voltage B-C Over Vbc HS 1021 Volts D 010
11 Over Voltage C-A Over Vca HS 1022 Volts D 010
12 Over Voltage N-G Over Vng HS 1027 Volts E 010
13 Under Voltage A–N Under Van HS 1024 Volts D 020
14 Under Voltage B–N Under Vbn HS 1025 Volts D 020
15 Under Voltage C–N Under Vcn HS 1026 Volts D 020
16 Under Voltage A-B Under Vab HS 1020 Volts D 020
17 Under Voltage B–C Under Vbc HS 1021 Volts D 020
18 Under Voltage C–A Under Vca HS 1022 Volts D 020
19-20 Reserved for custom alarms —————
Disturbance Monitoring (1/2 Cycle)
01 Voltage Swell A Swell Van 4 Volts D 080
02 Voltage Swell B Swell Vbn 5 Volts D 080
03 Voltage Swell C Swell Vcn 6 Volts D 080
04 Voltage Swell N–G Swell Vng 7 Volts E 080
05 Voltage Swell A–B Swell Vab 1 Volts D 080
06 Voltage Swell B–C Swell Vbc 2 Volts D 080
07 Voltage Swell C–A Swell Vca 3 Volts D 080
08 Voltage Sag A–N Sag Van 4 Volts D 090
09 Voltage Sag B–NSagVbn5VoltsD090
10 Voltage Sag C–NSagVcn6VoltsD090
11 Voltage Sag A–B Sag Vab 1 Volts D 090
12 Voltage Sag B–CSagVbc2VoltsD090
13 Voltage Sag C–ASagVca3VoltsD090
14 Current Swell A Swell Ia 8 Amperes A 080
15 Current Swell B Swell Ib 9 Amperes A 080
16 Current Swell C Swell Ic 10 Amperes A 080
17 Current Swell N Swell In 11 Amperes B 080
18 Current Sag A Sag Ia 8 Amperes A 090
19 Current Sag B Sag Ib 9 Amperes A 090
20 Current Sag C Sag Ic 10 Amperes A 090
Table 6–3: List of Default Alarms by Alarm Number
Alarm
Number
Alarm Description
Abbreviated
Display Name
Test
Register
Units
Scale
Group
Alarm
Type
Alarm Types are described in Table 6–4 on page 96.