Appendix AAbbreviated Register Listing 63230-300-212
Register Listing April 2001
© 2001 Schneider Electric All Rights Reserved
134
1231 Current Fundamental Coincident Angle, Phase A 0.1 ° 0to3,599
1232 Current Fundamental RMS Magnitude, Phase B A Amps/Scale 0 to 32,767
1233 Current Fundamental Coincident Angle, Phase B 0.1 ° 0to3,599
1234 Current Fundamental RMS Magnitude, Phase C A Amps/Scale 0 to 32,767
1235 Current Fundamental Coincident Angle, Phase C 0.1 ° 0to3,599
1236 Current Fundamental RMS Magnitude, Neutral B Amps/Scale 0 to 32,767
1237 Current Fundamental Coincident Angle, Neutral 0.1 ° 0to3,599
1238 Current Fundamental RMS Magnitude, Ground C Amps/Scale 0 to 32,767
1239 Current Fundamental Coincident Angle, Ground 0.1 ° 0to3,599
1244 Voltage Fundamental RMS Magnitude, A-N/A-B D Volts/Scale 0 to 32,767
1245 Voltage Fundamental Coincident Angle, A-N/A-B 0.1 ° 0to3,599
1246 Voltage Fundamental RMS Magnitude, B-N/B-C D Volts/Scale 0 to 32,767
1247 Voltage Fundamental Coincident Angle, B-N/B-C 0.1 ° 0to3,599
1248 Voltage Fundamental RMS Magnitude, C-N/C-A D Volts/Scale 0 to 32,767
1249 Voltage Fundamental Coincident Angle, C-N/C-A 0.1 ° 0to3,599
1250 Voltage Fundamental RMS Magnitude, N-G E Volts/Scale 0 to 32,767
1251 Voltage Fundamental Coincident Angle, N-G 0.1 ° 0to3,599
1255 Fundamental Real Power, Phase A F kW/Scale -32,767 to 32,767
1256 Fundamental Real Power, Phase B F kW/Scale -32,767 to 32,767
1257 Fundamental Real Power, Phase C F kW/Scale -32,767 to 32,767
1258 Fundamental Real Power, Total F kW/Scale -32,767 to 32,767
1259 Fundamental Reactive Power, Phase A F kVAr/Scale -32,767 to 32,767
1260 Fundamental Reactive Power, Phase B F kVAr/Scale -32,767 to 32,76
1261 Fundamental Reactive Power, Phase C F kVAr/Scale -32,767 to 32,767
1262 Fundamental Reactive Power, Total F kVAr/Scale -32,767 to 32,767
1264 Distortion Power, Phase A F kW/Scale -32,767 to 32,767
1265 Distortion Power, Phase B F kW/Scale -32,767 to 32,767
1266 Distortion Power, Phase C F kW/Scale -32,767 to 32,767
1267 Distortion Power, Total F kW/Scale -32,767 to 32,767
1268 Distortion Power Factor, Phase A 0.10% 0 to 1,000
1269 Distortion Power Factor, Phase B 0.10% 0 to 1,000
1270 Distortion Power Factor, Phase C 0.10% 0 to 1,000
1271 Distortion Power Factor, Total 0.10% 0 to 1,000
1274 Harmonic Current, Phase A A Amps/Scale 0 to 32,767
1275 Harmonic Current, Phase B A Amps/Scale 0 to 32,767
1276 Harmonic Current, Phase C A Amps/Scale 0 to 32,767
Table A3:Abbreviated Register List
Register
Number
Description
Scale
Factor
Units Register Range
See How Power Factor is Stored in the Registeron page 128.
The alternate storage method for power factor (PF) is useful for outputting PF on analog outputs. The PF value is stored as a positive value
between 0 and 2, centered around 1 (unity). A value of 0 lagging maps to0; -0.999 maps to 0.999;0.999 leadingmaps to 1.001; and 0 leading
maps to 2. The alternate PF is also stored with a scale factor 0.001.
These configuration registers require that you enter the setup mode to change the registers contents. Issue command 9020 to enter setup
mode and 9021 to exit setup mode. See Using the Command Interface to Change Configuration Registerson page 187 for instructions on
howtousethesetup-modecommands.
Quantity available for 4-wire system only. Value set to -32,768 if not available.